Load-Bearing Capacity Study of the Central Tower of the Correos Building (Madrid)

Building Projects

Load-Bearing Capacity Study of the Central Tower of the Correos Building (Madrid)

Back to list
Estudio Capacidad Portante Torreón de Correos (Madrid) – foto 2Estudio Capacidad Portante Torreón de Correos (Madrid) – foto 3

Project description


In August 1998, José A. Torroja, Oficina Técnica S.A. was commissioned to study the load-bearing capacity of the steel structure of the central tower of the Palacio de Comunicaciones, as part of the restoration and rehabilitation of its stone façades.

The floor structure of the octagonal Central Tower rests on eight battened columns made of UPN sections, filled with brick and cement mortar. Around the perimeter, the columns carry built-up girders, and on these rest main beams, also built-up. All plate connections are made with riveted angles. The floor spans one way, with IPN joists 0.70 m apart. The whole structure is statically determinate, with pinned connections.

As a first step, a detailed inspection of the structure was carried out, which revealed widespread corrosion in many elements, as well as delamination, flaking and loss of steel section at some joints and beams. To carry out these inspections, openings were made at the joints, exposing all eight joints of the structure.

This corrosion is caused partly by the external environment and partly by moisture in areas of gypsum mortar, which attacks the steel. It was therefore recommended to clean the rust off the beams, apply protective paint and finally re-clad the structure.

In addition, the load-bearing capacity of the structure was recalculated for the current loads. The conclusion was that, since the strengths obtained in the material tests were similar to those assumed in the design, the structure is in an acceptable state of safety and no strengthening work is required.